Skip to content

Generator problems

ATS Not Switching to the Generator or Back to Mains

The short answer

If the generator runs but the automatic changeover (ATS) will not take the load, will not hand back when the mains returns, or chatters between the two, the fault is usually in the mains sensing, the controller’s mode or timer settings, or the contactors or motorised switch that do the switching. Check that the controller is in automatic and note any alarm, but leave the panel closed: it is live from both supplies. The repair is technician work, and knowing which step of the sequence failed points straight to the part.

  • Check the controller is in automatic mode and note any alarm
  • A short delay before switching, and a cool-down run after, are normal
  • Load shedding wears contactors: every outage means two transfers
  • Never open the panel, force a contactor or bypass the interlock
Yellow Turner Morris silent diesel generator with an ATS panel, installed in a brick alcove

Need it fixed rather than diagnosed?

Free callouts and quotations. We arrive within 1–2 hours, usually within 1 hour.

How it should work

The normal changeover sequence

Knowing the sequence makes it easier to see where it stops. The delays are set on the controller and vary between installations.
  1. 01

    Mains fails

    The controller senses that the mains is lost or out of limits on any phase, and starts a short delay so brief dips do not start the generator.

  2. 02

    Generator starts and settles

    The engine starts and runs until its voltage and frequency are stable and within limits.

  3. 03

    Load transfers to the generator

    The changeover disconnects the mains and connects the generator. Interlocks make sure the two are never connected at once.

  4. 04

    Mains returns

    The controller waits until the mains has been stable for a set time before acting.

  5. 05

    Load transfers back

    The changeover disconnects the generator and reconnects the mains.

  6. 06

    Cool-down and stop

    The generator runs unloaded for a few minutes to cool down, then stops and waits for the next outage.

Timeline with three lanes: mains, generator and the supply to the load. 1: the mains fails and a start delay ignores brief dips. 2: the generator starts and settles. 3: the load transfers to the generator. 4: the mains returns and a return delay checks it is stable. 5: the load transfers back to the mains. 6: the generator runs unloaded to cool down, then stops.
What an automatic changeover does during a power cutOpen full size (opens in a new tab)

Where is the sequence going wrong?

Match what you see to the step that failed. The repair route shows where the fault is usually found.
Where is the sequence going wrong?
SymptomLikely causesRepair route
Generator does not start when the mains failsLikely causesController in manual or off, a flat battery, a mains-sensing fault, an active shutdown alarmRepair routeGenerator not starting
Generator runs, but the ATS never takes overLikely causesGenerator voltage or frequency outside the transfer limits, a failed contactor coil or switch motor, a blown control fuse, an interlock fault, a long transfer delayRepair routeATS and controller repair
Will not hand back when the mains returnsLikely causesLong return delay, mains sensing not seeing the supply (blown sensing fuse or a missing phase), a failed mains contactor coil, a stuck mechanismRepair routeMains sensing and contactor checks
Changeover chatters or switches back and forthLikely causesUnstable or low returning mains, delays set too short, a contactor coil supply sagging below pull-in, loose control wiringRepair routeSettings and coil supply checks
Generator starts while the mains is onLikely causesOne mains phase missing or low, a blown sensing fuse, or a scheduled exercise runRepair routeMains sensing repair
Generator keeps running after switching backLikely causesNormal cool-down; if it never stops, a stop solenoid, fuel solenoid or controller faultRepair routeStop circuit checks
Only some circuits work on generator powerLikely causesThose circuits are not wired to the generator side, a phase is missing, or a breaker has trippedRepair routeRunning but no power
Manual changeover switch hot, buzzing or discolouredLikely causesLoose or burnt terminals, worn contacts, or a switch too small for the loadRepair routeSwitch off and call us

Causes explained

The parts that make a changeover work

  • The controller and its mode: Control panel repairs

    The generator controller (often a DSE, ComAp or SmartGen unit) or a separate ATS controller decides when to start, transfer and stop. Left in manual or stop after a service or a test run, it will not respond to an outage.

  • Mains sensing

    The controller watches each mains phase through small fuses or breakers. If one blows, it thinks the mains has failed when it has not, so it starts the generator with the mains on or refuses to hand back. Single-phase sensing on a three-phase site can miss a lost phase altogether.

  • Contactors or a motorised switch

    The switching is done by a pair of contactors or a motorised changeover switch. Coils burn out, contacts pit and weld, and mechanisms stick, especially if they rarely operate. A contactor coil is often fed from the supply it connects, so a weak supply leaves it buzzing or dropping out.

  • Interlocks

    Mechanical and electrical interlocks stop the mains and the generator ever being connected together. A faulty interlock, or a welded contact on one side, blocks the transfer completely.

  • The generator’s output: Voltage problems

    The controller transfers only when the generator’s voltage and frequency are within limits. A set that hunts or runs at low voltage may keep running without ever taking the load, or stop on an alarm.

  • Manual changeover switches

    Many homes and small businesses have a manual changeover: someone starts the generator and moves the switch. Worn or loose switches overheat at their terminals, and an undersized one runs hot under load.

SmartGen genset controller in the control panel of an open diesel generator canopy, with the engine and cable entries visible
A SmartGen controller in a generator control panel

Controller settings

Timer settings that look like faults

Every step of the sequence has an adjustable delay on the controller: how long the mains must be gone before the start, how long the engine warms up, when the load transfers, how long the mains must be stable before handing back, and how long the engine cools down. Correct values can still look like a fault to someone waiting in the dark, and wrong values cause real faults.

A long return delay keeps the building on the generator for many minutes after the neighbours’ lights come back. A short one lets the ATS hand back to a supply that is still settling, which causes chatter. An exercise timer can start the set on a quiet Sunday with the mains on. Settings should be changed only by someone who knows the site, because they interact with UPS units, lifts, pumps and other loads.

  • Start delay: ignores brief dips
  • Return delay: proves the mains is stable
  • Cool-down: runs unloaded before stopping
  • Exercise timer: scheduled test runs

Load shedding is hard on changeovers

An ATS that once switched a few times a year can switch several times a day during load shedding: once when the power goes and again when it returns. Each transfer under load draws an arc across the contacts, so contacts pit and burn, coils run hot and mechanisms wear far sooner than on a set that covers the odd outage. A contactor that chatters or hesitates is often worn out rather than faulty.

The return of the mains is the other stress. Power often comes back unstable, low during the evening peak, or with a surge as a whole area reconnects at once. If the return delay is too short, the ATS hands back to a supply that then dips, and it transfers again, over and over. Return delays set for the site, surge protection on the mains side and a contactor check at every maintenance visit go a long way to preventing it.

What you can check without opening the panel

All of these are done from the outside of the panels, without opening any covers.

  • The generator controller shows automatic mode (not manual, test or off); note any alarm text
  • The generator’s voltage and frequency on the controller look normal
  • The battery charger shows it is powered, and the controller screen is not blank or restarting
  • The generator’s output breaker is on
  • Any indicator lights on the changeover panel showing which supply is available or connected
  • Whether the mains is off for the whole street or only for your property
  • How long you waited after the mains failed or returned, compared with what normally happens
  • Any burning smell, buzzing or heat from the changeover panel: if so, stop and call us

If the generator is running and the building is still dark after several minutes, call us with a photo of the controller screen. For a site that cannot wait, book emergency generator repair. We arrive within 1–2 hours (usually within 1 hour).

Changeover repairs and what they involve

Changeover repairs and what they involve
Cause foundWhat the repair involves
Controller left in manual or offWhat the repair involvesReturn it to automatic and find out why it was changed
Mains sensing fuse blown or a phase missingWhat the repair involvesReplace the fuse, check the sensing wiring and find out why it failed
Contactor coil burnt or contacts pittedWhat the repair involvesReplace the contactor, and check the other side’s contacts and the coil supply
Motorised changeover stuck or failedWhat the repair involvesRepair or replace the motor or mechanism, then test both directions
Interlock faultWhat the repair involvesRepair the mechanical and electrical interlock and test transfer both ways
Controller fault or wrong configurationWhat the repair involvesRepair or replace the controller and set it up for the site
Delays set unsuitablyWhat the repair involvesSet the delays to suit the site, the loads and the local mains
Worn or overheating manual switchWhat the repair involvesReplace the switch with one rated for the load, and re-make the terminals
Changeover undersized or badly installedWhat the repair involvesQuote for a replacement through generator installation

Testing a changeover properly

Starting the generator from the controller proves the engine runs, but not that it will take over in an outage. A proper test simulates a mains failure, so the whole sequence runs: sensing, start, transfer, return and cool-down. Where it is safe and agreed with you, our maintenance plans include one, and where full-load proof is needed, a load bank test can be arranged to show the generator can carry the building once it takes over.

Installing, altering or replacing a changeover is part of the building’s electrical installation and must comply with the wiring regulations, so it is handled as an installation job rather than a repair. See generator installation for how that works.

FAQ

Frequently asked questions

Why is my ATS not switching to the generator?

Usually because the controller does not see the generator as ready (its voltage or frequency is out of limits), the controller is not in automatic, or the generator-side contactor or motorised switch has failed. The controller screen often shows which; send us a photo when you call.

Why does the generator take a while to come on after the power goes off?

A short delay is deliberate. The controller waits to make sure the outage is real, then lets the generator settle before switching the load over. If the delay seems much longer than usual, ask us to check the settings.

The power is back. Why is the generator still running?

After switching back to the mains, most generators run unloaded for a few minutes to cool down before stopping. If it keeps running well beyond that, there is a fault in the stop circuit or the controller.

Why did my generator start when the power was still on?

Most often one mains phase has failed or dropped low, which the controller treats as a mains failure. A blown sensing fuse or a scheduled exercise run can also start it.

Why does my changeover keep switching back and forth?

Chatter usually means the returning mains is unstable or low, the delays are set too short, or a contactor is not getting enough voltage to pull in firmly. Switch off sensitive loads and call us: chattering contacts burn quickly.

Can I switch over by hand if the automatic changeover fails?

Only if the panel has a manual selector or changeover switch on its outside, designed for that purpose, and you have been shown how to use it. Never open the panel or push contactors in by hand; if you are unsure, call us.

Need a generator technician?

  • 24/7 operations
  • We Arrive Within 1–2 Hours (usually within 1 hour)
  • Free callouts and quotations
Call nowWhatsApp us