Low, High or Fluctuating Voltage from Your Generator

The short answer

Wrong voltage from a generator comes from one of four places: the excitation system (the AVR, its sensing and the rotating diodes), the engine’s speed, the load, or the wiring between the set and your equipment. When it happens (all the time, only under load, or each time a motor starts) and whether every phase is affected tells you which. Until it is fixed, switch off computers, televisions and chargers, and reduce the load.

  • Note whether the voltage is low, high, swinging or collapsing
  • Note whether it changes with load or when motors start
  • On three-phase sets, compare all three phase readings
  • Check the frequency too: a speed fault shows up as a voltage fault
Firman FPG5800M petrol generator with a voltmeter and sockets on its panel and an AVR alternator label on the tank

Need it fixed rather than diagnosed?

Free callouts and quotations. We arrive within 1–2 hours, usually within 1 hour.

What the voltage reading points to

Read the voltage on the controller or panel meter while the problem is happening, and note what was running at the time.
What the voltage reading points to
SymptomLikely causesRepair route
Low at every load, frequency normalLikely causesAVR voltage setting drifted, a weak AVR or exciter, a failed rotating diode, a poor connection in the AVR supply or exciter leadsRepair routeAVR tests and set-up
Low, and the frequency is low tooLikely causesThe engine is running slow and the AVR is lowering the voltage on purpose: a governor or fuel fault, or overloadRepair routeFix the engine speed first
Collapses when load is switched onLikely causesOverload, a shorted rotating diode, a self-excited AVR losing its supply on a heavy load step, an engine bogging downRepair routeLoad, diode and excitation tests
Deep dip when a pump, compressor or air conditioner startsLikely causesMotor starting current too large for the set, or slow AVR or governor responseRepair routeSizing and motor starting
High voltage, lights unusually brightLikely causesBroken or loose sensing lead, a failed AVR driving full excitation, a wrong setting, or power-factor-correction capacitors left in circuit at light loadRepair routeSwitch off, then AVR and wiring checks
Voltage swings, lights flicker or pulseLikely causesEngine speed hunting, AVR stability set wrongly, a loose connection, or a large load cycling on and offRepair routeSpeed and stability checks
One phase high, another lowLikely causesBadly unbalanced single-phase loads, single-phase AVR sensing, or a loose or broken neutral (dangerous)Repair routeSwitch off, then call us
Correct at the generator, low at a far buildingLikely causesVoltage drop in a long or undersized cable to an outbuilding, borehole pump or gate motorRepair routeCable check by an electrician

Causes explained

What lies behind each kind of voltage fault

  • When the voltage is low: AVR repairs

    The AVR holds whatever value it is set to, so a drifted setting leaves every reading low while the regulator works perfectly. A poor connection in its supply or exciter leads, or a failed rotating diode, can also leave it unable to reach the set value. More often the engine is to blame: many AVRs deliberately reduce the voltage when speed falls below a set point, to protect the exciter. Fuel starvation or an overloaded engine pulls the speed down, the regulator follows it, and replacing the regulator changes nothing.

  • When the voltage is high

    High voltage does the most damage. If the AVR’s sensing lead breaks or works loose, the regulator sees too little voltage and drives the exciter harder; some AVRs shut down when they lose sensing, but not all. A failed AVR can also stick at full output. On business premises, power-factor-correction capacitors on a lightly loaded set can push the voltage up as well.

  • When it swings or the lights flicker: Surging and hunting

    Rhythmic swinging usually follows the engine: if the governor hunts, frequency and voltage hunt together. If the frequency holds steady while the voltage moves, the AVR stability setting, a loose connection or a load that switches on and off is more likely. The eye picks up even small, rhythmic changes in brightness, so flickering lights are often the first sign.

  • When it collapses under load

    A healthy set dips briefly as load comes on and recovers within a second or two. If it collapses and stays down, the set may be overloaded, the engine may be bogging down, or a shorted rotating diode may be limiting excitation. A self-excited AVR draws its power from the output itself, so a very heavy load step can starve it; sets with a PMG hold up better.

What to do while the voltage is wrong

These steps protect your equipment and give us the readings that point to the cause.

  • Switch off computers, televisions, chargers and other sensitive electronics
  • Reduce the load and watch whether the voltage settles
  • Note the voltage on each phase, and the frequency, from the controller
  • Note what was running or starting when it went wrong
  • Start large motors such as pumps, compressors and air conditioners one at a time
  • Check whether the problem is at every socket or only in one building or circuit

If the frequency is also wrong, the engine’s speed is the likely cause: see generator surging and hunting.

Two panels. Single phase: one live conductor and neutral, 230 V live to neutral, used in homes, small shops and portable generators. Three phase: three live conductors 120 degrees apart, 230 V from each phase to neutral and 400 V between phases, used by businesses, factories and large sets. On a three-phase set, single-phase loads should be spread evenly across the phases.
Single phase and three phase comparedOpen full size (opens in a new tab)

Three-phase sets: unbalanced loads and the neutral

On a three-phase set, a home or office is usually fed as single-phase circuits shared across the three phases. If most of the load ends up on one phase (the kitchen, the geysers and a borehole pump, say), that phase sags while the lightly loaded ones rise. Many AVRs sense only one phase, so they hold that phase correct and let the other two drift. A three-phase-sensing AVR averages all three, but it still cannot correct a badly unbalanced load. Our guide to single- and three-phase power explains the basics.

The cure is to rebalance the circuits across the phases, which is electrician’s work in the distribution board. A loose or broken neutral is more serious: loads on different phases end up in series across 400 V, so the lightly loaded side can see far more than 230 V and appliances fail within seconds.

  • Spread single-phase loads across all three phases
  • Single-phase sensing hides the other two phases
  • Bright and dim rooms at the same time: suspect the neutral

How the type of set and load shedding change the picture

Small single-phase units that use a capacitor instead of an AVR regulate less tightly, so their voltage moves more with load by design; a sudden change in that behaviour points to the capacitor or the windings. Inverter generators produce a stable electronic output, so a voltage problem on one usually means overload or an inverter module fault. Three-phase standby sets are the ones most affected by unbalanced loads and by AVR or sensing faults.

Load shedding adds two patterns of its own. When the changeover transfers, the generator takes everything that was left switched on at once, so fridges, pumps and air conditioners start together and the dip can trip equipment or stall a motor. Later, in the evening, the set may run for hours with little connected, and a governor or AVR that is only just stable at light load shows up as lights that pulse. Mention either pattern when you call, because each points the diagnosis in a different direction.

Diagnosis

How we track down a voltage fault

  1. 01

    Speed before voltage

    Frequency at no load and under load. If the engine cannot hold its speed, that is repaired first.

  2. 02

    Measure at both ends

    Voltage at the alternator terminals and at the affected equipment separates generator faults from cabling faults.

  3. 03

    Step the load

    Readings as load is applied in stages show whether the voltage dips and recovers properly, collapses or swings.

  4. 04

    Check excitation and sensing

    AVR settings, sensing and supply wiring, the rotating diodes and the neutral connection.

How each voltage fault is repaired

How each voltage fault is repaired
Cause foundWhat the repair involves
AVR setting driftedWhat the repair involvesReset voltage and stability at rated speed, then confirm under load
AVR failed or sensing lead brokenWhat the repair involvesRepair the wiring, or fit and set up a matching regulator: see AVR repairs
Shorted rotating diodeWhat the repair involvesReplace the diode set, then check the AVR it has been overworking
Engine speed low or huntingWhat the repair involvesRepair the governor or the fuel system first, then re-check the voltage
Unbalanced loadWhat the repair involvesRebalance circuits across the phases (electrician)
Motor starting dipsWhat the repair involvesStagger starts, fit soft starters on large motors, or size a larger set
Cable voltage dropWhat the repair involvesLarger cable on the affected circuit
Loose or broken neutralWhat the repair involvesRepair by a qualified electrician, then check what was damaged
Capacitors pushing the voltage highWhat the repair involvesArrange for power-factor correction to switch out while on generator power

Where a repair needs proof at full load, a load bank test can be arranged and quoted.

FAQ

Frequently asked questions

What voltage should a generator give in South Africa?

Nominally 230 V between live and neutral, and 400 V between phases on a three-phase set, at 50 Hz. A few volts of movement as the load changes is normal; most equipment is designed for a supply within about 10% either side of 230 V.

Why do my lights flicker on generator power?

Usually because the engine speed or the AVR is not holding steady, a connection is loose, or a large load is switching on and off. It should be checked, because unstable voltage also stresses electronics.

Can low or high voltage damage my equipment?

Yes. Motors draw more current at low voltage and overheat, and some electronics behave erratically. High voltage is worse: it can destroy chargers, televisions and control boards quickly, sometimes before anyone notices the lights are too bright.

Is a voltage dip when my borehole pump starts normal?

A brief, shallow dip is normal. A deep dip that stalls the pump, trips a breaker or makes lights go out means the generator is struggling with the starting current.

Why is the voltage different on each phase?

Usually because the load is unbalanced across the phases. If the difference is large or appeared suddenly, switch off and have the neutral checked, because a broken neutral destroys appliances.

Can I adjust the AVR to raise the voltage?

No. The trimmers sit in a live terminal box, and low voltage is often a speed or wiring fault that the AVR is correctly responding to. Turning it up hides the cause and can overload the exciter. Our guide to what an AVR does explains why.

Need a generator technician?